The Ei603RF heat alarm has a sealed 10 year lithium battery designed to last the full lifetime of the alarm with a built-in RadioLINK+ module allowing it to wirelessly interlink with other RadioLINK and RadioLINK+ devices, ensuring occupants have the earliest possible warning of a fire in the property. Heat alarms detect fire by sensing the rise in temperature in their surroundings rather than sampling the air, meaning the Ei603RF is suitable for the loft, kitchen, or garage where dust and fumes may cause nuisance alarms with other types of detector.
The table below shows all the units that can interlink with the EI603RF.
Smoke and Heat Alarms
Model Number
|
Type of Unit
|
Type of Interlink
|
Ei3014RF | Mains Powered Heat Alarm - Sealed Lithium | Radio Interlink |
Ei3016RF | Mains Powered Optical Smoke Alarm - Sealed Lithium | Radio Interlink |
Ei3024RF | Mains Powered Optical & Heat Alarm - Sealed Lithium | Radio Interlink |
Ei3028RF | Mains Powered Heat & Carbon Monoxide Alarm - Sealed Lithium | Radio Interlink |
Ei2110eRF | Mains Powered Multi Sensor Smoke & Heat Alarm - Sealed Lithium | Radio Interlink |
Ei161eRF | Mains Powered Ionisation Smoke Alarm - Sealed Lithium | Radio Interlink |
Ei164eRF | Mains Powered Heat Alarm - Sealed Lithium | Radio Interlink |
Ei166eRF | Mains Powered Optical Smoke Alarm - Sealed Lithium | Radio Interlink |
Ei168RC/141RC | Mains Powered Ionisation Alarm - 9V Alkaline | Radio Interlink |
Ei168RC/144RC | Mains Powered Heat Alarm - 9V Alkaline | Radio Interlink |
Ei168RC/146RC | Mains Powered Optical Smoke Alarm - 9V Alkaline | Radio Interlink |
Ei3100RF | Battery Powered Ionisation Smoke Alarm - 9V Alkaline | Radio Interlink |
Ei3103RF | Battery Powered Heat Alarm - 9V Alkaline | Radio Interlink |
Ei3105RF | Battery Powered Optical Smoke Alarm - 9V Alkaline | Radio Interlink |
Ei603RF | Battery Powered Heat Alarm - Sealed Lithium | Radio Interlink |
Ei650RF | Battery Powered Optical Smoke Alarm - Sealed Lithium | Radio Interlink |
Carbon Monoxide Alarms
Model Number
|
Type of unit
|
Type of interlink
|
Ei3018RF | Mains Powered Carbon Monoxide Alarm - Sealed Lithium | Radio Interlink |
Ei3028RF | Mains Powered Heat & Carbon Monoxide Alarm - Sealed Lithium | Radio Interlink |
Ei262 | Mains Powered Carbon Monoxide Alarm - Sealed Lithium | Radio Interlink |
Ei208WRF | Battery Powered Carbon Monoxide Detector - Sealed Lithium | Radio Iinterlink |
Ancillary Products
Model Number
|
Type of unit
|
Type of interlink
|
Ei170RF | Mains Powered Strobe and Vibration Pad for the Hearing Impaired - Sealed Lithium | Radio Interlink |
Ei450 | Battery Powered Fire and CO Alarm Controller - Sealed Lithium | Radio Interlink |
Ei411H | Battery Powered Locate, Silence & Test Control Switch - Sealed Lithium | Radio Interlink |
Ei407 | Battery Powered Manual Call Point - Sealed Lithium | Radio Interlink |
Ei410TRF | Battery Powered Test Remote - Sealed Lithium | Radio Interlink (Ei3100RF Series) |
Ei428 | Mains Powered 5A Relay Module | Radio Interlink |
Y03 | Mains Powered Multi Frequency Sounder | Hardwire Interlink (via relay) |
SAB300C | Mains Powered Flashing Xenon Strobe (Clear) | Hardwire Interlink (via relay) |
SAB300R | Mains Powered Flashing Xenon Strobe (Red) | Hardwire Interlink (via relay) |
Wiring Explained
Mains powered Ei Electronics smoke and heat alarms require a 230V AC power supply and up to 12 alarms can be hardwire interlinked in one system.
To obtain a mains power supply, each alarm can be connected to the nearest lighting circuit using 2 core and earth cable with a separate, dedicated interlink cable connecting alarms where applicable. However, if possible it is recommended that any alarms connected via interlink cable are all powered from a dedicated circuit from the distribution board using 3 core and earth cable for safety during maintenance, as the interlink cable will carry power from live alarms on other power circuits. Please see the diagram below:-
This is the technical data for the Radio-Interlinked Heat Alarm with Sealed Ten Year Lithium Battery - Ei603RF.
Product Code | EI603RF |
---|---|
Alternative Product Codes | EI603RF, EI603, Ei603, Ei603C, Ei603CRF, Ei603TYCRF |
Weight | 0.28kg |
Sensor Type | Thermistor - activates at 58°C |
Dimensions (HxDia) | 55x115mm |
Battery Type | Sealed 10 Year Lithium |
Sound Output | 85dBA at 3 meters |
Radio Linking Frequency | 868.499MHz |
Radio-Frequency Range | Clear Line of Sight: 100m Typical Property: 30m |
Temperature Range | Operating: 0°C to +40°C Storage: 0°C to +35°C |
Humidity Range | 15% to 95% Relative Humidity |
The following datasheets are available for this product.
Q. Please could you explain how the repeater function works on the Aico/Ei radio interlinked detectors.
A. Hello. The radioLINK repeater function allows the smoke alarm to "repeat" the radio frequency signal around obstructions. This stops the signal from becoming blocked and ensures that all interlinked alarms can be reached. This repeater function is built-in to the the Ei168RC radioLINK base (with Ei140, Ei160 or Ei2110 alarm), the Ei600 series of radio interlinked battery powered smoke and heat alarms as well as the Ei262 and Ei208WRF carbon monoxide alarms as standard. When house coded, the system works itself out which alarms are to act as repeaters - it's not something you set up yourself.
Q. What is the difference between Ei3100RF radio-interlinked smoke alarm series and the Ei600 series of radio-interlinked smoke alarms? Why does one cost much more than the other?
A. The EI600RF series are a later model and on top of all the features that the Ei3100RF offers, the series has the possibility to use the locate feature in the control switch, making the product more similar to a BS5839 part 6 Grade A alarm system. Additionally, the Ei600 series smoke alarms are offered with a true ten year life sealed lithium battery which makes the alarms acceptable in most circumstances as a BS5839 part 6 Grade D fire alarm system. This offers a substantial saving to customers, as it replaces the need for an electrician installing mains powered alarms.
Q. If the radio interlinking signal on one unit fails will the units still work as stand alone units.
A. Yes, should the radio interlinking signal fail the units will continue to sound independently should they detect a fire.
Q. Can a wireless router interfere with the radio interlinked alarms?
A. A wireless router is very unlikely to interfere with the signal of your radio interlinked alarms, as the RF signal of the smoke alarms is digitally coded.
Q. Do the radio interlinked units give out a constant signal all the time and does this decrease the battery life more than a non-interlinked alarm?
A. Yes, radio interlinked alarms are periodically sending and receiving signals from other units in the network and therefore the life of the battery is reduced. Units with alkaline batteries should have the batteries are changed annually [unless they are fitted with a sealed 10 year battery as eg in the Ei600RF series].
Show all FAQsModel | Stock | Price | Weight |
---|---|---|---|
Product Code: EI603RF |
Stock Level:
9 in stock Expected dispatch: Today
|
Price:
£131.03 inc VAT £109.19 ex VAT |
Weight:
0.28kg
|
2 customers have rated this product and it has an overall rating of 5 out of 5
Reviewed by: KF
Fantastic product. Very easy to install. Would recommend.
Published on: 9th February 2018
The following delivery options are available on this product.
If you have any questions or would like more information about this product you can ask one of our specialists.