Contact
Sales & Customer Service
0800 612 6537 support@safelincs.co.uk Live ChatDelivery Enquiries
0800 077 6149 - Resources
Discontinued Product
This product has been discontinued.
£130.39 inc VAT
£108.66 ex VAT
The Ei605CRF is a 9V alkaline battery powered radio-interlinked optical smoke alarm. Using the built-in RadioLINK module the Ei605CRF can be wirelessly interlinked with up to 11 other Aico and Ei Electronics products, while the stylish design ensures that these detectors never look out of place and are suitable for modern installations.
Product Code | EI605CRF |
---|---|
Alternative Product Codes | EI605CRF, EI605, EI605RF, EI605TYC, EI605TYCRF, EI605C |
Brand | EI Electronics |
Battery Life | Approximately 12 months |
Battery Type | 9V PP3 Alkaline |
Dimensions (HxDia) | 55x115mm |
Operating Temperature | Operating: 0°C to +40°C Storage: 0°C to +35°C |
Radio Linking Frequency | 868.499MHz |
Radio-Frequency Range | Clear Line of Sight: 100m Typical Property: 30m |
Relative Humidity | 15% to 95% Relative Humidity |
Sensor Type | Optical Smoke Sensor |
Sound Output | 85dB |
Weight | 0.20kg |
Product Datasheets |
The manufacturer's recommendation is to test the alarm by pressing the test button. This will simulate a heat input at the heat sensor. You can also test it with a hair dryer but make sure that the hairdryer is kept away at a suitable distance from the alarm. Do not attempt to test the alarm by using open fire or excessive heat as this may damage the unit.
Yes this entirely possible. The Ei140 series with RF base is mains powered and these are compatible to interlink with the battery operated Ei3100 series. Please view the interconnection overview on either of these alarms for further details.
The Ei600 series of radio-interlinked alarms are completely battery operated. This means that they do not need to be wired up to the mains circuit. On the website, we offer the Ei600 series with a standard 9v battery or with a 10 year lithium longlife battery. The standard 9V batteries last approximately 12-18 months depending on how often the detectors are tested. The lithium battery units are sealed and last 10 years i.e. the full lifespan of the detector.
If one alarm was to malfunction the other units would not be affected, if it was due to alarm failure. If the fault was with the radio-interlinking signal, then all alarms that are in the chain after the faulty alarm would be affected and they would not go off.
The Ei605TYCRF comes with a ten year lithium battery, this should last for the life span of the alarm. The Ei605CRF comes with an alkaline battery that will need to be changed every 12 months. As these alarms are part of the Ei600 series they are both compatible with the Ei412.
Yes, radio interlinked alarms are periodically sending and receiving signals from other units in the network and therefore the life of the battery is reduced. Units with alkaline batteries should have the batteries are changed annually [unless they are fitted with a sealed 10 year battery as eg in the Ei600RF series].
Yes, should the radio interlinking signal fail the units will continue to sound independently should they detect a fire.
The EI600RF series are a later model and on top of all the features that the Ei3100RF offers, the series has the possibility to use the locate feature in the control switch, making the product more similar to a BS5839 part 6 Grade A alarm system. Additionally, the Ei600 series smoke alarms are offered with a true ten year life sealed lithium battery which makes the alarms acceptable in most circumstances as a BS5839 part 6 Grade D fire alarm system. This offers a substantial saving to customers, as it replaces the need for an electrician installing mains powered alarms.
Hello. The radioLINK repeater function allows the smoke alarm to "repeat" the radio frequency signal around obstructions. This stops the signal from becoming blocked and ensures that all interlinked alarms can be reached. This repeater function is built-in to the the Ei168RC radioLINK base (with Ei140, Ei160 or Ei2110 alarm), the Ei600 series of radio interlinked battery powered smoke and heat alarms as well as the Ei262 and Ei208WRF carbon monoxide alarms as standard. When house coded, the system works itself out which alarms are to act as repeaters - it's not something you set up yourself.
If you have any questions or would like more information about this product you can ask one of our specialists.
Live Chat Available Now