-
Contact
Sales & Customer Service
0800 612 6537 support@safelincs.co.uk Live ChatDelivery Enquiries
0800 077 6149 - Resources
The Ei3016 is a mains powered optical smoke alarm with built in, self-charging back-up battery to provide power in the event of a mains outage. Fitted with a high performance optical smoke sensor, most suitable for detecting slow, smouldering fires, the alarm also contains an integrated insect screen and automatic dust compensation measures to reduce the number of false alarms. Fitted with AudioLINK technology, the Ei3016 allows you to extract real time data from the alarm directly to your smart phone. It is also compatible with the Ei3000MRF SmartLINK module which allows for radio-interlinking between alarms.
Please Note: The Ei3000MRF SmartLINK module for radio-interlinking is sold separately.
The tables below show all the products that can interlink with the Ei3016.
More products may be compatible when installed in conjunction with the Ei3000MRF SmartLINK module. Please see the Ei3016RF bundle for further information.
Smoke and Heat Alarms
Model Number
|
Type of Unit
|
Type of Interlink
|
Ei3014 / Ei3014RF | Mains Powered Heat Alarm - Sealed Lithium | Hardwire Interlink |
Ei3016 / Ei3016RF | Mains Powered Optical Smoke Alarm - Sealed Lithium | Hardwire Interlink |
Ei3024 / Ei3024RF | Mains Powered Optical & Heat Alarm - Sealed Lithium | Hardwire Interlink |
Ei3028 / Ei3028RF | Mains Powered Heat & Carbon Monoxide Alarm - Sealed Lithium | Hardwire Interlink |
Ei2110e / Ei2110eRF | Mains Powered Multi Sensor Smoke & Heat Alarm - Sealed Lithium | Hardwire Interlink |
Ei161e / Ei161eRF | Mains Powered Ionisation Smoke Alarm - Sealed Lithium | Hardwire Interlink |
Ei164e / Ei164eRF | Mains Powered Heat Alarm - Sealed Lithium | Hardwire Interlink |
Ei166e / Ei166eRF | Mains Powered Optical Smoke Alarm - Sealed Lithium | Hardwire Interlink |
Ei141 / Ei168RC141RC | Mains Powered Ionisation Alarm - 9V Alkaline | Hardwire Interlink |
Ei144 / Ei168RC144RC | Mains Powered Heat Alarm - 9V Alkaline | Hardwire Interlink |
Ei146 / Ei168RC146RC | Mains Powered Optical Smoke Alarm - 9V Alkaline | Hardwire Interlink |
Carbon Monoxide Alarms
Model Number
|
Type of unit
|
Type of interlink
|
Ei3018 / Ei3018RF | Mains Powered Carbon Monoxide Alarm - Sealed Lithium | Hardwire Interlink |
Ei3028 / Ei3028RF | Mains Powered Heat & Carbon Monoxide Alarm - Sealed Lithium | Hardwire Interlink |
Ei261 | Mains Powered Carbon Monoxide Alarm - Sealed Lithium | Hardwire Interlink |
Ancillary Products
Model Number
|
Type of unit
|
Type of interlink
|
MCP401RC | Mains Powered Manual Call Point | Hardwire Interlink |
Ei1529RC | Mains Powered Locate, Silence & Test Control Switch | Hardwire Interlink |
Ei159 | Mains Powered Smoke Alarm Locator Switch | Hardware Interlink |
Ei128R | Mains Powered 5A Relay Module | Hardwire Interlink |
Ei128RBU | Mains Powered 5A Relay Module with Lithium Backup Battery | Hardwire Interlink |
Y03 | Mains Powered Multi Frequency Sounder | Hardwire Interlink (via relay) |
SAB300C | Mains Powered Flashing Xenon Strobe (Clear) | Hardwire Interlink (via relay) |
SAB300R | Mains Powered Flashing Xenon Strobe (Red) | Hardwire Interlink (via relay) |
Wiring Explained
Mains powered Ei Electronics smoke and heat alarms require a 230V AC power supply and up to 12 alarms can be hardwire interlinked in one system.
To obtain a mains power supply, each alarm can be connected to the nearest lighting circuit using 2 core and earth cable with a separate, dedicated interlink cable connecting all alarms. However, if possible it is recommended that the alarms are all powered from a dedicated circuit from the distribution board using 3 core and earth cable for safety during maintenance, as the interlink cable will carry power from live alarms on other power circuits. Please see the diagram below:-
Product Code | EI3016 |
---|---|
Brand | EI Electronics |
Back-Up Battery | Self-charging Lithium Battery |
Dimensions (HxDia) | 55 x 150mm |
Operating Temperature | 0°C to 40°C |
Relative Humidity | 15% to 95% |
Sound Output | 85dB |
Warranty | 5 Years |
Weight | 0.40kg |
Product Datasheets |
BS 5839-6 recommends that one or two storey HMOs with an individual floor area of no more than 200sqm (not the total of both floors) should have a Grade D smoke alarm system installed. Grade D refers to mains powered smoke alarms with a back up battery power supply. The alarms can be interlinked either by wire or by radio signal and the system does not require a separate fire alarm panel. For HMOs of 3 storey or higher, a Grade A panel system would need to be installed. This can cover the whole of the building, or can be used just for the communal areas with a separate Grade D system installed for the individual dwellings. For both applications, the level of cover should be a minimum of LD3 (in all escape routes) but this may change according to the fire risk assessment.
Model | Stock | Price |
---|---|---|
Product Code: EI3016 |
Stock Level:
More than 20 in stock Expected dispatch: Today
|
Price:
£53.99 inc VAT £44.99 ex VAT |
Approved Partner
The following delivery options are available on this product.
6 customers have given this product an overall rating of 4.8 out of 5
Rating: 5 / 5 Stars
Reviewed by: R T
Simple quick installation
Published on: 13th February 2023
Rating: 5 / 5 Stars
Reviewed by: S E
Simple install Quick and easy to install. Quick delivery service and great price.
Published on: 2nd August 2022
Rating: 4 / 5 Stars
Reviewed by: I S
professionally installed and works fine Excellent advice from safelincs website which advised this as a replacement for an old BRK model no longer available in this country.
Published on: 18th July 2022
If you have any questions or would like more information about this product you can ask one of our specialists.
Live Chat Available Now