The Syncro AS single loop addressable fire alarm panel from Kentec is capable of running up to 126 Apollo devices, with each given a unique address for ease of identification when the system has been activated. Its large graphical display and clear control button layout allow for installers, engineers and end users to easily configure and maintain the addressable panel when needed. The Kentec Syncro AS panel offers a range of configuration options as well as a number of programmable inputs and relays, giving the fire alarm system the flexibility to adapt to various commercial applications.
- Certified to BS EN 54 Part 2 and Part 4
- Features a single detection loop capable of running 126 devices
- Allocates an individual address to each device
- 40 characters available to give each device a name and/or location
- Identifies the exact detector or device that has activated the fire alarm system
- The single detection loop can be split into 16 zones as needed
- Supports Apollo Series 90, XP95 & Discovery protocol
- Large graphical display and clear button and indicator layout
- Features 5 programmable inputs, 3 relays and 2 sounder circuits
- Keypad configuration access
- Available with or without Kentec software USB memory stick
- A range of configurable options such as day/night sensitivity and cause and effect action
- Can be connected with up to 15 Kentec Syncro View repeater panels
- Available with or without 2 x 12V, 7Ah stand-by batteries. Panel requires stand-by batteries to operate
Technical Data
This is the technical data for the Kentec Syncro AS Addressable Single Loop Panel - 16 Zone.
Dimensions (HxWxD) |
310x385x90mm |
Operating Temperature |
-5 °C to +35 °C |
IP Rating |
IP30 |
Construction |
1.2mm mild sheet steel |
Supply Voltage |
230V AC |
Number of Zones |
16 |
Product Datasheets
The following datasheets are available for this product.