Aico Ei2110 Multi-Sensor Smoke and Heat Alarm - Safelincs - Approved supplier for Ei Electronics
Basket (0) Checkout
FREEPHONE 0800 612 6254 Now FREE from UK mobiles

Mains Powered Combined Smoke and Heat Alarm with Lithium Battery - Ei2110e

9 in stock
61.43 inc VAT
51.19 ex VAT
Product Overview

The Ei2110e is a multi-sensor fire alarm that contains two separate sensing elements – optical and heat detection. As the unit monitors two different by-products of fires (smoke and temperature), its response to all types of fire is vastly improved over traditional single sensor alarms. It is also less prone to false alarms.

  • Suitable for living rooms, bedrooms, hallway, landings (not suitable for kitchen or garage)
  • 230V Hard-wired smoke and heat alarm
  • Multiple sensor elements - optical and heat detectors
  • Unique dust compensation feature (The alarm automatically adjusts for any contamination within the optical sensor chamber)
  • Kitemarked to BS EN 14604:2005
  • Suitable for installations complying to BS 5839-6: 2013 Grade D, E and F
  • CE Marked
  • 5 year guarantee
  • Tamper-proof rechargeable 10 year lithium battery back-up
  • Advanced suppression and calibration technology reduces risk of false alarms to absolute minimum
  • Low battery warning
  • Test/Hush button
  • Easy-fit base
  • A maximum of 12 units can be interlinked
  • Supplied with fixings; 2 x screws and 2 x rawl plugs
  • Alarms that can be interlinked with include:
  • Remote control capability using the Ei1529RC
Interlink

The table below shows all the units that can interlink with the EI2110.

Compatible Alarms
Model Number
Type of unit
Type of interlink
Ei161e Ionisation Alarm Hard wire using 3 core cable
Ei161RC Ionisation Alarm Hard wire using 3 core cable
Ei164e Heat Alarm Hard wire using 3 core cable
Ei164RC Heat Alarm Hard wire using 3 core cable
Ei166e Optical Alarm Hard wire using 3 core cable
Ei166RC Optical Alarm Hard wire using 3 core cable
Ancillary Products
Model Number
Type of unit
Type of interlink
Y03 Multi Frequency Sounder Hard wire using 3 core cable
MCP401RC Manual Call Point Hard wire using 3 core cable
Ei1529RC Smoke alarm Locate, Hush and Remote test switch Hard wire using 3 core cable

Wiring Explained

The Ei2110 multi-sensor alarm requires a 230V AC mains power supply. Up to 12 Ei2110 and Ei160 series of alarms can be hard wire interlinked on one circuit.

To obtain a mains feed, the first alarm can be connected to the nearest lighting circuit using 2 core and earth cable. From this alarm, 3 core and earth cable is required for all additional alarms, which allows for the hard wire interlink to work. Please see the diagram below:-


wiring-hard-wired-alarms

Alternatively, the alarms can be hard wired using a dedicated circuit from the distribution board.

Technical Data

This is the technical data for the Mains Powered Combined Smoke and Heat Alarm with Lithium Battery - Ei2110e.

Product Code EI2110E
Alternative Product Codes Ei2110, Ei2110e
Weight 0.32kg
Dimensions (HxDia) 152x50mm
Back-Up Battery Rechargeable Lithium
Sound Output 85dB (minimum) at 3m
Temperature Range 0C to 40C
Humidity Range 15% to 95% Relative Humidity

Data Sheets

Pricing & Availability

Model Stock Levels Price Weight
Product Code: EI2110E Stock Level:
9 in stock
Price:

61.43 inc VAT

51.19 ex VAT

Weight:
0.32kg

Delivery Options

The following delivery options are available on this product.

Economy Delivery

Delivered in 3-7 working days by Royal Mail 4.68 inc VAT - More info

Next Day Delivery

Delivered the next working day by UK Mail from 7.80 inc VAT - More info

For delivery on order within

Looking for more information?

If you have any questions or would like more information about this product you can ask one of our specialists.

Direct Telephone 01507 464181
Direct Email Email Now